ElectraCalcIQ

Engineering-caliber calculations

Load Calculator Demo

Try a Load Calc for a service or feeder -- connected load, demand factor, voltage, phase, and power factor. No signup required.

Calculation Metadata

You can calculate freely right now. Create an organization to save results to a project.
Optional for live results and save.

Inputs

Method: connected load times demand factor gives demand kW; service current is I = (Demand kW * 1000) / (V * PF) for single-phase, or / (V * sqrt(3) * PF) for three-phase. The full calculator supports NEC Article 220 load categories, largest-motor uplift, and branded PDF / XLSX export.

Load
System

Results

Connected load 150.0kW
Demand load 127.5kW
Service current 170.4A
System voltage 480.0V

Math window

  1. Compute demand load: Demand kW = 150.0 * 0.85 = 127.5
  2. Compute service current: I = (127.5 * 1000) / (480.0 * sqrt(3) * 0.9) = 170.4

Need NEC Article 220 load categories and stamped PDF export?

The full ElectraCalcIQ Load Calculator supports itemised NEC Article 220 categories, largest-motor uplift, saved projects, and branded PDF / XLSX export for stamped submittals.

Start free trial

Math Window

Formulas

  1. Demand load
    Demand kW = Connected kW * Demand Factor
    Units: kW
  2. Service current
    I = (Demand kW * 1000) / (V * sqrt(3) * PF)
    Units: A
  3. Power factor assumption
    Power factor (PF) = 0.9.

Ordered Steps

  1. Compute demand load
    Demand kW = 150.0 * 0.85
    Result: 127.5
    Units: kW
  2. Compute service current
    I = (127.5 * 1000) / (480.0 * sqrt(3) * 0.9)
    Result: 170.4
    Units: A

Engineering Use Notice

Calculator outputs are provided as engineering support and workflow aid. They do not replace licensed professional judgment, project-specific design review, or code-required responsibility.

See full details in the Engineering Disclaimer.